抄録
Air-conditioning (AC) system consumes high energy and releases waste-heat. In the present study, we propose a method to improve its performance and minimize waste-heat by replacing existing air-cooled condenser by an evaporation and transpiration, evapo-transpiration, condenser. The improvement is confirmed by performing experiment for a conventional air-cooled AC system and a water-cooled AC system. Condenser temperature in the air-cooled system is higher than outdoor-temperature by 5-10 C, while it is -5 to 5 C in case of the testing system. From simulation results, saving energy consumption is expected to reach up to 30% in summer with the testing system. Based on these results, an evapo-transpiration heat-exchanger was developed as a new condenser. Heat-transfer coefficient of the testing heat-exchanger is at least 4 times higher than that of air-cooled condenser. Even hot fluid is used inside copper-tubing, its outlet-air temperature is as nearly as outdoor temperature.